Resistive Load Bank Manufacturers & Exporters

POWERTRON manufactures resistive load bank systems in India for generator commissioning, UPS proving, battery discharge testing and DC system verification, built around punched Fechral grid resistor elements rated for a 375°C temperature rise. A resistive load bank is the simplest and most robust way to present a genuine, known load to a power source — no electronics in the load path, no failure modes that need firmware to diagnose, and no dependence on a grid connection to absorb the energy. That is precisely why it remains standard equipment for site commissioning and acceptance testing, where the priority is proving the source performs under real load rather than characterising it dynamically. Elements are supplied in standard punched grid box sizes from A1 through D6, in AC and DC configurations, with ratings and enclosures built to the installation. Manufactured in-house at Wagle Estate, Thane.

Resistive load bank

Resistive load bank

Resistive load bank

Resistive load bank

Key Features of POWERTRON Resistive Load Banks :

  • Punched Fechral grid resistor elements rated to 375°C temperature rise — a proven high-temperature alloy that tolerates repeated thermal cycling without the resistance drift that degrades test accuracy over a bank’s life.
  • Duty-factor rated current tables — every resistance value is specified at 25%, 40%, 60% and 100% ED, so the bank can be correctly sized for intermittent commissioning work or for continuous load soaking rather than guessed at.
  • Standard grid box sizes from A1 to D6 — a documented dimensional range that lets the bank be laid out against available floor or enclosure space before manufacture rather than after.
  • No electronics in the load path — the load is the resistance itself, which means no firmware, no control failure modes, and predictable behaviour in the field where a commissioning engineer cannot afford diagnostics.
  • Independent of the grid — energy is dissipated locally, so no export permission, no grid connection capacity requirement and no interaction with site supply quality.
  • Wide resistance range from 0.01 to 2.5 ohms per element — banks are configured to the voltage and current of the actual source rather than to a fixed catalogue step.
  • AC and DC configurations — the same construction serves generator and UPS acceptance testing on the AC side and battery, rectifier and DC system testing on the DC side.
  • Built to the installation — enclosure, cooling, mounting and control arrangement configured to the site rather than supplied as a fixed product.

Technical Specifications — Resistive Load Bank

Parameter Specification What It Means For You
Element Type Punched Fechral grid resistors High-temperature alloy tolerant of repeated thermal cycling
Temperature Rise Rating 375°C Current ratings are stated against a defined thermal condition
Resistance Range 0.01 to 2.5 ohms per element Banks configured to the actual source voltage and current
Current Rating Duty-factor dependent — see the 25/40/60/100% ED chart Correct sizing for intermittent or continuous duty
Grid Box Sizes A1, A2, B1, B2, C1-C6, D1-D6 Dimensional planning possible before manufacture
Box Dimensions 430mm to 880mm width, 280mm to 1680mm height Layout confirmed against available floor or enclosure space
Configuration AC and DC Generator and UPS testing, or battery and rectifier testing
Power Rating Built to requirement Sized to the source being tested, not to a catalogue step
Control Step switching, contactor or manual Matched to whether the bank is operated on site or in a test cell
Cooling Forced air or natural convection by rating Selected against duty and installation environment
Enclosure Built to installation — indoor, outdoor, trailer or containerised Site-appropriate rather than a fixed format

Resistance Boxes

Dimensions Details of Punched Fechra Resistance Boxes
Unit Size A a b Unit Size A a b H
A1 430 380 360 B1 580 530 510 280
A2 430 380 360 B2 580 530 510 560
C1 730 680 650 D1 880 830 805 280
C2 730 680 650 D2 880 830 805 560
C3 730 680 650 D3 880 830 805 840
C4 730 680 650 D4 880 830 805 1120
C5 730 680 650 D5 880 830 805 1400
C6 730 680 650 D6 880 830 805 1680

Resistance Boxes

Rated Values (Ohms) Current Rating for Various Duty Factors (AMPS)
25% ED 40% ED 60% ED 100% ED
0.01 666 488 420 352
0.015 550 404 350 290
0.022 450 330 286 238
0.032 374 276 230 198
0.046 314 228 196 166
0.068 256 190 166 136
0.1 212 156 132 112
0.15 174 136 110 92
0.22 144 108 90 76
0.3 120 96 76 66
0.46 98 72 62 52
0.72 78 60 50 42
1 64 50 42 38
1.5 56 40 36 30
2.5 40 30 24 20
Duty Factor Meaning When It Applies
25% ED Energised one quarter of the time Short-burst step testing, brief acceptance checks, intermittent proving
40% ED Energised roughly two fifths of the time Routine commissioning sequences with cooling intervals between steps
60% ED Energised roughly three fifths of the time Extended commissioning, multi-step generator acceptance runs
100% ED Continuously energised Full-duration load soaking, endurance testing, continuous burn-in
Sizing consequence Current capacity falls as duty rises A 0.1 ohm element carries 212A at 25% ED but only 112A continuously — nearly half. Size against the longest continuous period the test actually requires.

How a Regenerative Load Bank Works

A resistive load bank is exactly what its name says — a bank of precisely known resistances that can be connected to a power source in defined combinations to draw a defined load. There is no conversion stage and no electronics in the load path. The source sees a real resistance, current flows according to Ohm’s law, and the energy becomes heat in the elements.

The element is where the engineering sits. Punched grid resistors are made from sheet alloy stamped into a serpentine pattern, which gives a large surface area for heat rejection in a compact envelope and allows the resistance value to be set precisely by the geometry of the punch. Fechral — an iron-chromium-aluminium alloy — is used because it holds its resistance value through repeated heating to several hundred degrees without the drift that would gradually corrupt test accuracy.

Current capacity is a thermal question rather than an electrical one. An element carrying current heats up; how much current it can carry depends on how long it stays energised and how effectively the heat is removed. That is why the rating chart on this page gives four different current figures for the same resistance value at 25%, 40%, 60% and 100% duty factor. Elements are grouped into standardised grid boxes, and boxes are combined and switched — manually, by contactor, or in programmed steps — to build the load profile the test procedure requires.

Applications of Regenerative Load Banks

Regenerative load banks are justified wherever test duty is long, repetitive or high-power — the payback comes from hours of operation, not from the purchase. Short, occasional commissioning tests are usually better served by a resistive bank.

Industry Application Why Resistive Rather Than Regenerative
Power Transmission Substation DC system and battery discharge verification No grid export permission needed at a live substation
Telecom & Data Centre UPS, generator and rectifier plant acceptance testing Simple, robust, no interaction with critical site supply
Railway & Transportation Trackside and depot standby power commissioning Field-deployable with no grid connection dependency
Aerospace Ground power unit and generator proving Predictable load with no control electronics to fail
Medical Equipment Hospital standby generator statutory testing Straightforward periodic compliance testing
Solar & Wind Site commissioning where export is not yet permitted Testing possible before grid connection is energised
Electronics Manufacturing Power supply burn-in and endurance soaking Continuous duty at low capital cost
Petrochemical Emergency generator and DC backup commissioning Hazardous-area installations where simplicity is a safety asset

Resistive vs Regenerative vs Programmable Load Bank

Criteria Resistive Load Bank Regenerative Load Bank Programmable Load Bank
Energy handling Dissipated as heat Returned to the grid Dissipated as heat
Capital cost Lowest Highest Moderate
Running cost Highest Lowest over long duty Moderate
Grid dependency None — works anywhere Requires a grid connection to export into None
Export permission Not required May be required by the licensee Not required
Complexity No electronics in the load path Four-quadrant converter and digital control Digital electronic load
Control modes Fixed resistance steps CR, CV, CC, CP CV, CC, CR, CP
Field deployability Highest — trailer and container builds Fixed installation Bench and rack
Best fit Site commissioning, acceptance, statutory testing Long-duration high-power laboratory testing Component and bench-level electronic loading

How to Select a Resistive Load Bank

  • Source rating to be tested — kW or kVA, and whether it is AC or DC. This is the starting point and the page currently does not ask for it.
  • Test voltage and current — a load bank sized in kW still has to match the voltage of the source, since resistance is fixed by both together.
  • Longest continuous energised period — this sets the duty factor, and the duty factor roughly halves the usable current between 25% ED and continuous operation.
  • Load steps required — how finely the load must be adjustable, which determines how the elements are grouped and switched.
  • Control arrangement — manual switching, contactor stepping, or programmed sequencing from a controller.
  • Installation environment — indoor test cell, outdoor site, trailer-mounted for mobile commissioning, or containerised for a permanent yard installation.
  • Heat rejection — where the dissipated energy goes. Indoors, the full test power appears as heat the building must extract, which is often the decisive constraint.
  • Ambient and altitude — both affect cooling and therefore the achievable rating at a given element size.

Custom Regenerative Load Bank Builds

Resistive load banks are, by nature, built rather than picked from a catalogue. POWERTRON configures the element grouping, switching arrangement, enclosure and cooling to the source being tested and the environment it is tested in. Standard grid box sizes from A1 through D6 provide the building blocks; the bank is assembled from them to the required power, voltage and step resolution.

Enclosure options run from indoor cabinet through outdoor weatherproof, trailer-mounted for mobile commissioning work, and containerised for permanent yard installations. Control can be manual switching for simple acceptance testing, contactor stepping for repeatable sequences, or a programmed controller with data logging for statutory testing that requires a record. Share the source rating, voltage, duty cycle, step resolution and installation environment for a configuration proposal and quotation.

Manufacturing, Quality and Export Capability

POWERTRON INDIA PVT. LTD. designs and manufactures its complete power conversion range at Plot No. A-426/427, Road No. 28, Wagle Estate MIDC, Thane West 400604, Maharashtra. Design, magnetics, PCB assembly, enclosure fabrication and full-load testing are all carried out in-house, which is what allows both short lead times and real engineering support after the sale rather than component-level replacement only.

Every unit is tested on load across its full operating envelope before dispatch, with the test record supplied against the serial number. The company holds ISO, CE and BIS certifications, is MSME registered and GeM listed, and manufactures under the Make in India framework — making POWERTRON a practical import substitute for organisations currently sourcing from overseas. Domestic sales and service offices operate in Delhi, Pune, Hyderabad, Bangalore and Tamil Nadu, with international offices in Dubai, Singapore and Malaysia supporting export customers across the Middle East, Southeast Asia, Africa and Europe.

Frequently Asked Questions — Resistive Load Bank

What is a resistive load bank used for? +

It presents a known, real load to a power source so the source can be proven to deliver its rated output. The most common uses are generator commissioning and acceptance testing, UPS proving, battery discharge verification and DC system testing at substations and data centres.

What does ED mean on the current rating chart? +

ED is duty factor — the proportion of time the elements are energised. The same resistance element carries substantially more current on intermittent duty than continuously. A 0.1 ohm element is rated at 212A at 25% ED but 112A at 100% ED, so sizing against the wrong duty factor nearly doubles the error.

Why Fechral grid resistors rather than wire elements? +

Punched grid elements give a large heat-rejecting surface area in a compact envelope and allow the resistance to be set precisely by the geometry of the punch. Fechral holds its resistance value through repeated heating to several hundred degrees, so test accuracy does not drift over the life of the bank.

Should I buy resistive or regenerative? +

Resistive if the testing is occasional, site-based, or in a location with no grid connection to export into — commissioning and statutory testing typically fall here. Regenerative if testing is long-duration, high-power and repetitive, where recovering the energy pays back the higher capital cost.

Where does all the heat go? +

Into the surrounding air. On an indoor installation the full test power appears as heat the building ventilation must remove, which is frequently the constraint that decides the installation location. Outdoor, trailer-mounted and containerised builds avoid the problem entirely.

Can it be used for DC as well as AC? +

Yes. The same construction serves both. AC configurations are used for generator and UPS acceptance testing; DC configurations for battery discharge, rectifier plant and substation DC system verification.

Can the load be adjusted in steps during a test? +

Yes. Elements are grouped into switchable banks, and the step resolution is set at design. Switching can be manual for simple acceptance work, contactor-based for repeatable sequences, or controller-driven with data logging where a test record is required.

Can it be supplied trailer-mounted or containerised? +

Yes. Mobile builds for commissioning contractors and containerised builds for permanent yard installations are both supplied. State the installation environment at enquiry as it affects enclosure, cooling and element rating.

What information do you need to quote? +

Source rating in kW or kVA, AC or DC, test voltage and current, the longest continuous energised period, required load step resolution, control arrangement, and the installation environment including ambient temperature.

Need a Resistive Load bank?

Request a quotation for a resistive load bank. Send your source rating, AC or DC, test voltage and current, duty cycle, required step resolution and installation environment to sales@powertrondcps.com, or call +91 8097707496 / +91 7208560460. Every resistive load bank is configured to the application.

Instagram Facebook E-mail Youtube Linkedin