Regenerative Load Bank Manufacturers & Exporters

POWERTRON manufactures regenerative load bank systems in India from 60kW to 250kW, covering 10-1000V and up to 1000A, for test facilities where dissipating the test energy as heat is no longer acceptable. A conventional resistive load bank converts every watt of test power into heat that then has to be extracted from the building. A regenerative load bank instead returns that energy to the grid through a four-quadrant PWM converter, at better than 93% efficiency and 0.99 power factor, with input harmonics held under 3%. On a battery, EV or drive test bench running continuously, that is the difference between paying twice for the same energy and paying once. High-speed digital control delivers 0.1% output accuracy across constant resistance, voltage, current and power modes, and the modular construction allows capacity to be added without replacing the installation. Manufactured in-house at Wagle Estate, Thane, Maharashtra.

Regenerative Load Bank

Regenerative Load Bank

Key Features of the POWERTRON Regenerative Load Bank :

  • Four-quadrant control with bidirectional energy flow — test energy is returned to the grid rather than dissipated as heat, which removes both the electricity cost and the extraction load on the building HVAC.
  • Better than 93% efficiency with 0.99 power factor and under 3% input harmonics — PWM rectification means the unit behaves as a well-mannered load on the incoming supply rather than as a harmonic source the facility then has to correct.
  • Four programmable modes — constant resistance, constant voltage, constant current and constant power, with fast transient response, so one unit covers battery discharge, drive loading, inverter testing and power supply validation.
  • High-speed digital control delivering 0.1% output accuracy — the loading condition is exactly what the test procedure specifies, which is what makes results defensible in a qualification report.
  • Automatic line voltage drop compensation — the load condition seen at the device under test is the programmed one, not the one that survived the cable run.
  • 10-inch touchscreen — set points, live measurement and stored profiles on one screen, which shortens operator training on a complex multi-mode instrument.
  • Programmable output and protection parameters — protection thresholds are set to the DUT rather than to the load bank rating, protecting expensive battery packs and drive systems.
  • International components throughout, including LEM current sensing and Infineon power devices — the parts a maintenance engineer can source anywhere.
  • Modular construction — capacity is added or a module is swapped without replacing the installation, and maintenance does not require the whole unit to come off line.

Technical Specifications — Regenerative Load Bank

Parameter Specification What It Means For You
Power Range 60, 80, 100, 120, 150, 200 and 250 kW Component bench through to full pack and drive-level test cells
Voltage Range 10–600V, 10–800V and 10–1000V by model Covers 400V and 800V EV architectures and industrial DC buses
Rated Current 600A, 800A and 1000A Current rating selected independently of voltage and power
Energy Flow Four-quadrant, bidirectional, grid-returning Test energy recovered instead of dissipated as heat
Efficiency Greater than 93% Under 7% of test energy lost rather than 100%
Power Factor 0.99 via PWM rectification No penalty on the facility supply, no correction equipment needed
Input Harmonics Less than 3% Compliant behaviour on the incoming grid connection
Operating Modes Constant resistance, voltage, current and power One instrument covers battery, drive, inverter and PSU testing
Accuracy 0.1% output accuracy, high-speed digital control Loading condition matches the test specification exactly
Transient Response Fast response across all four modes Dynamic load profiles reproduced, not just static steps
Compensation Automatic line voltage drop compensation Programmed condition delivered at the DUT terminals
Interface 10-inch touchscreen Single-screen operation of a multi-mode instrument
Components LEM sensing, Infineon power devices Internationally sourceable spares
Construction Modular Scalable capacity and module-level maintenance

Available Variants

Model number Rated Power Voltage Range Rated Current
PIPL-150-800-600-RLB 150kW 10~800V 600A
PIPL-150-800-800-RLB 10~800V 800A
PIPL-150-800-1000-RLB 10~800V 1000A
PIPL-150-1000-600-RLB 10~1000V 600A
PIPL-150-1000-800-RLB 10~1000V 800A
PIPL-150-1000-1000-RLB 410~1000V 1000A
PIPL-200-800-600-RLB 200kW 10~800V 600A
PIPL-200-800-800-RLB 10~800V 800A
PIPL-200-800-1000-RLB 10~800V 1000A
PIPL-200-1000-600-RLB 10~1000V 600A
PIPL-200-1000-800-RLB 10~1000V 800A
PIPL-200-1000-1000-RLB 10~1000V 1000A
PIPL-250-800-600-RLB 250kW 10~800V 600A
PIPL-250-800-800-RLB 10~1000V 800A
PIPL-250-800-1000-RLB 10~800V 1000A
PIPL-250-1000-600-RLB 10~1000V 600A
PIPL-250-1000-800-RLB 10~1000V 800A
PIPL-250-1000-1000-RLB 10~1000V 1000A
PIPL-060-600-600-RLB 60kW 10~600V 600A
PIPL-060-600-800-RLB 10~600V 800A
PIPL-060-600-1000-RLB 10~600V 1000A
PIPL-060-1000-600-RLB 10~1000V 600A
PIPL--060-1000-800-RLB 10~1000V 800A
PIPL-060-1000-1000-RLB 10~1000V 1000A
PIPL-080-800-600-RLB 80kW 10~800V 600A
PIPL-080-800-800-RLB 10~800V 800A
PIPL-080-800-1000-RLB 10~800V 1000A
PIPL-080-1000-600-RLB 10~1000V 600A
PIPL-080-1000-800-RLB 10~1000V 800A
PIPL-080-1000-1000-RLB 10~1000V 1000A
PIPL-080-800-600-RLB 100kW 10~800V 600A
PIPL-080-800-800-RLB 10~800V 800A
PIPL-080-800-1000-RLB 10~800V 1000A
PIPL-080-1000-600-RLB 10~1000V 600A
PIPL-080-1000-800-RLB 10~1000V 800A
PIPL-080-1000-1000-RLB 10~1000V 1000A
PIPL-120-800-600-RLB 120kW 10~800V 600A
PIPL-120-800-800-RLB 10~800V 800A
PIPL-120-800-1000-RLB 10~800V 1000A
PIPL-120-1000-600-RLB 10~1000V 600A
PIPL-120-1000-800-RLB 10~1000V 800A
PIPL-120-1000-1000-RLB 10~1000V 1000A

Which Regenerative Load Bank Do You Need?

Power Voltage Options Current Typical Application
60 kW 10–600V, 10–1000V 600 / 800 / 1000 A Module-level battery testing, small drive and inverter validation
80 kW 10–800V, 10–1000V 600 / 800 / 1000 A Battery pack testing, mid-size drive loading, PSU qualification
100 kW 10–800V, 10–1000V 600 / 800 / 1000 A EV pack cycling, renewable inverter testing, telecom rectifier plant
120 kW 10–800V, 10–1000V 600 / 800 / 1000 A Traction component loading, larger inverter and converter testing
150 kW 10–800V, 10–1000V 600 / 800 / 1000 A Vehicle-level EV testing, railway sub-system loading
200 kW 10–800V, 10–1000V 600 / 800 / 1000 A High-power drive and traction test cells, grid-tie equipment testing
250 kW 10–800V, 10–1000V 600 / 800 / 1000 A Full test facility installations, multi-station laboratories

How a Regenerative Load Bank Works

A regenerative load bank presents itself to the device under test as a programmable load, exactly as a resistive bank would — but what happens to the energy afterwards is completely different. Instead of routing it into resistor elements and turning it into heat, the load bank draws it into a DC stage and then feeds it back into the AC grid through a four-quadrant PWM converter operating in reverse.

The four-quadrant description is the key. A conventional rectifier moves power in one direction only, from AC to DC. A four-quadrant converter handles both current directions at both voltage polarities, which means the same power stage that would draw energy from the grid can equally push energy into it. The controller keeps the returned current synchronised and in phase with the grid, which is what produces the 0.99 power factor and holds input harmonics below 3%.

On the load side, a high-speed digital control loop samples voltage and current continuously and adjusts the converter to hold whichever mode is programmed. In constant resistance mode it holds the ratio of voltage to current; in constant current it holds current regardless of voltage; in constant power it trades the two off; in constant voltage it holds terminal voltage. Switching between modes is a firmware operation, not a hardware change.

The economic consequence is straightforward. A 250kW resistive bank running eight hours consumes 2,000 kWh and produces 2,000 kWh of heat the building must then remove. The same test on a regenerative bank at 93% efficiency returns roughly 1,860 kWh to the grid and produces only the balance as heat.

Applications of Regenerative Load Banks

Regenerative load banks are justified wherever test duty is long, repetitive or high-power — the payback comes from hours of operation, not from the purchase. Short, occasional commissioning tests are usually better served by a resistive bank.

Industry Application Mode Used Typical Power
Battery Manufacturing & Testing Pack and module discharge cycling, capacity verification CC / CP 60–250 kW
Automotive & EV Traction battery, inverter and charger loading CP / CR 100–250 kW
Aerospace Generator and power system qualification loading CC / CV 60–150 kW
Railway & Metro Traction converter and auxiliary supply loading CP 150–250 kW
Power Electronics R&D Converter, inverter and PSU characterisation All four modes 60–120 kW
Telecom & Data Centre Rectifier plant and UPS discharge testing CC / CR 60–200 kW
Solar & Wind Inverter and grid-tie equipment validation CP / CV 100–250 kW
Petrochemical Emergency generator and DC system commissioning CR / CP 100–250 kW

Regenerative vs Resistive vs Programmable Load Bank

Criteria Regenerative Load Bank Resistive Load Bank Programmable Load Bank
Energy handling Returned to the grid Dissipated as heat Dissipated as heat
Efficiency Over 93% recovered Zero recovery Zero recovery
Heat rejection Minimal Full test power as heat Full test power as heat
Running cost Lowest over long duty Highest Moderate
Capital cost Highest Lowest Moderate
Control modes CR, CV, CC, CP Fixed steps CV, CC, CR, CP
Power range 60–250 kW Custom, very high 1.2–40 kW
Dynamic response Fast Step switching only Up to 10 kHz dynamic
Best fit Long-duration, high-power, repetitive testing Commissioning, generator and UPS proving Bench and component-level electronic loading

How to Select a Regenerative Load Bank

  • Maximum test power and maximum test voltage, separately — a 250kW unit and a 1000V unit are different selections, and the model code carries power, voltage and current independently.
  • Peak current at the lowest test voltage — power divided by voltage gives the current the unit must actually deliver, which is what determines whether you need the 600A, 800A or 1000A variant.
  • Which control modes the test procedure calls for — battery work is usually CC or CP, drive loading tends to CP or CR, converter characterisation uses all four.
  • Duty cycle and daily operating hours — this is what determines the payback period against a resistive bank, and it is the number to build the business case on.
  • Grid connection available at the installation — voltage, phases and available capacity, since the unit both draws from and returns to that connection.
  • Utility permission for grid export — some distribution licensees require notification or approval for equipment that exports, even at low duty. Confirm early.
  • Dynamic profile requirements — whether the test steps load or follows a continuous profile, which determines the transient response needed.
  • Interface and data logging — whether results must feed an existing test-management system.

Custom Regenerative Load Bank Builds

The catalogue spans 60kW to 250kW at 600V, 800V and 1000V with 600A, 800A and 1000A current ratings, which is already 42 standard combinations. Beyond that, POWERTRON builds to specification: higher power ratings for full test-facility installations, extended voltage envelopes, parallel operation of multiple units under a single controller, and non-standard grid connection arrangements for sites with unusual supply configurations.

Because construction is modular, capacity expansion is designed in from the start — a facility can commission at one rating and add modules as test demand grows without replacing the installation. Firmware customisation covers application-specific load profiles, extended communication register maps for integration with an existing test-management system, and protection thresholds matched to the particular class of device under test. Share the power, voltage, current, mode and grid connection details for a firm proposal.

Manufacturing, Quality and Export Capability

POWERTRON INDIA PVT. LTD. designs and manufactures its complete power conversion range at Plot No. A-426/427, Road No. 28, Wagle Estate MIDC, Thane West 400604, Maharashtra. Design, magnetics, PCB assembly, enclosure fabrication and full-load testing are all carried out in-house, which is what allows both short lead times and real engineering support after the sale rather than component-level replacement only.

Every unit is tested on load across its full operating envelope before dispatch, with the test record supplied against the serial number. The company holds ISO, CE and BIS certifications, is MSME registered and GeM listed, and manufactures under the Make in India framework — making POWERTRON a practical import substitute for organisations currently sourcing from overseas. Domestic sales and service offices operate in Delhi, Pune, Hyderabad, Bangalore and Tamil Nadu, with international offices in Dubai, Singapore and Malaysia supporting export customers across the Middle East, Southeast Asia, Africa and Europe.

Frequently Asked Questions — Regenerative Load Bank

What is a regenerative load bank and how is it different from a resistive one? +

Both present a controlled load to the equipment under test. A resistive load bank turns all of that energy into heat. A regenerative load bank returns it to the AC grid through a four-quadrant converter at better than 93% efficiency, so the facility neither pays for the energy twice nor has to extract the heat.

How much energy does it actually recover? +

Better than 93% of test energy is returned. On a 250kW unit running an eight-hour shift, that is roughly 1,860 kWh of the 2,000 kWh consumed returned to the grid, with only the balance appearing as heat.

What power and voltage ranges are available? +

Standard models cover 60, 80, 100, 120, 150, 200 and 250kW, with voltage ranges of 10-600V, 10-800V and 10-1000V, and rated currents of 600A, 800A and 1000A. Higher ratings are built to order.

What control modes does it support? +

Constant resistance, constant voltage, constant current and constant power, all with fast transient response and 0.1% output accuracy. Switching between modes is a firmware operation, so one unit covers battery discharge, drive loading, inverter testing and power supply validation.

Will it disturb the grid connection at my facility? +

PWM rectification gives a 0.99 power factor and holds input harmonics below 3%, so the unit behaves as a well-mannered load and source on the incoming supply rather than as a harmonic problem the facility then has to correct.

Do I need utility permission to export energy back to the grid? +

Requirements vary by distribution licensee. Some require notification or approval for equipment that exports even at low duty. Raise this with your electricity supplier early, and the POWERTRON team can supply the technical documentation the application needs.

Is it suitable for battery pack testing? +

Yes, and it is one of the primary applications. Constant current and constant power modes with programmable protection thresholds allow controlled discharge cycling of packs and modules, with the discharge energy recovered rather than dissipated — which matters when a single characterisation run takes hours.

Can capacity be expanded later? +

Yes. Construction is modular, so a facility can commission at one rating and add modules as test demand grows without replacing the installation. The same modularity means maintenance can be done at module level.

How long does it take to pay back against a resistive load bank? +

It depends entirely on daily operating hours and local electricity tariff, since the saving accrues per kWh of test energy. Facilities running long-duration battery or drive testing typically see the shortest payback. Share your duty cycle and tariff and POWERTRON can work the calculation with you.

Need a Regenerative Load bank?

Request a quotation for a regenerative load bank. Send your maximum test power and voltage, peak current, required control modes, daily duty cycle and grid connection details to sales@powertrondcps.com, or call +91 8097707496 / +91 7208560460. POWERTRON quotes standard models from 60kW to 250kW and custom builds above.

Instagram Facebook E-mail Youtube Linkedin